TABLE T9 -
3.3(3.0)kV PVC or XLPE INSULATED CABLES, ARMOURED (COPPER CONDUCTOR)
(A) PVC INSULATED ARMOURED CABLE:
CURRENT- CARRYING CAPACITY (Amp)
Ambient temperature: 30°C
Ground temperature: 15°C
Conductor operating temperature: 70°C
Size of Conductor
In air
In single-way ducts
Laid direct in ground
3 single-core cable, trefoil
3 phase ac
3-core cable,
trefoil
3 phase ac
3 single-core cable, trefoil
3 phase ac
3-core cable,
trefoil
3 phase ac
3 single-core cable,
trefoil
3 phase ac
3-core cable,
trefoil
3 phase ac
1
2
3
4
5
6
7
mm²
A
A
A
A
A
A
16
79
80
94
25
102
105
120
35
126
125
145
50
181
153
190
145
190
175
70
228
191
225
180
235
215
95
284
233
265
220
280
260
120
326
274
295
250
315
295
150
372
312
320
280
350
330
185
423
353
355
315
395
375
240
502
419
395
365
455
430
300
567
474
430
405
510
480
400
642
549
455
465
560
540
500
716
490
610
630
809
530
660
800
874
550
690
1000
939
580
730
(B) XLPE INSULATED ARMOURED CABLE:
CURRENT- CARRYING CAPACITY (Amp)
Ambient temperature: 30°C
Ground temperature: 15°C
Conductor operating temperature: 90°C
Size of Conductor
In air
In single-way ducts
Laid direct in ground
3 single-core cable, trefoil
3 phase ac
3-core cable,
trefoil
3 phase ac
3 single-core cable, trefoil
3 phase ac
3-core cable,
trefoil
3 phase ac
3 single-core cable,
trefoil
3 phase ac
3-core cable,
trefoil
3 phase ac
1
2
3
4
5
6
7
mm²
A
A
A
A
A
A
16
105
95
115
25
138
120
145
35
166
145
175
50
233
200
220
175
225
205
70
290
252
270
215
275
255
95
352
309
315
255
325
305
120
409
361
345
295
370
345
150
466
409
380
330
415
385
185
532
470
420
370
465
435
240
627
551
470
425
530
500
300
713
627
510
480
590
560
400
817
540
660
500
912
580
720
630
1026
630
790