TABLE T1 - 1-CORE CABLES HAVING XLPE or LSHF INSULATION, NON-ARMOURED, WITH or WITHOUT SHEATH
(COPPER CONDUCTOR) 450/750V or 600/1000V
  Ambient temperature: 30°C
CURRENT- CARRYING CAPACITY (AMP) Conductor operating temperature: 90°C
Size of Conductor
Reference Method 4
(enclosed in conduit in
thermally insulating wall etc.)
Reference Method 3
(enclosed in conduit on a
wall or in trunking etc.)
Reference Method 1
(clipped direct)
Reference Method 11
(on a perforated cable tray,
horizontal or vertical)
Reference Method 12
(free air)
2-cables,
1 phase ac or dc
3 or 4 cables,
3-phase ac
2 cables,
1-phase ac or dc
3 or 4 cables,
3-phase ac
2 cables,
1-phase ac or dc flat & touching
3 or 4 cables,
3-phase ac flat & touching or trefoil
2 cables, 1-phase ac or dc flat & touching
3 or 4 cables,
3-phase ac
flat & touching or trefoil
3 cables trefoil,
3-phase ac
1
2
3
4
5
6
7
8
9
10
mm²
A
A
A
A
A
A
A
A
A
1.5
18
17
22
19
25
23
 
 
 
2.5
24
23
30
26
34
31
 
 
 
4
33
30
40
35
46
41
 
 
 
6
43
39
51
45
59
54
 
 
 
10
58
53
71
63
81
74
 
 
 
16
76
70
95
85
109
99
 
 
 
25
100
91
126
111
143
130
158
140
138
35
124
111
156
138
176
161
195
176
171
50
149
135
189
168
228
209
293
215
209
70
189
170
240
214
293
268
308
279
270
95
228
205
290
259
355
326
375
341
330
120
263
235
336
299
413
379
436
398
385
150
300
270
375
328
476
436
505
461
445
185
341
306
426
370
545
500
579
530
511
240
400
358
500
433
644
590
686
630
606
300
459
410
573
493
743
681
794
730
701
400
 
 
683
584
868
793
915
849
820
500
 
 
783
666
990
904
1044
973
936
630
 
 
900
764
1130
1033
1191
1115
1069
800
 
 
 
 
1288
1179
1358
1275
1214
1000
 
 
 
 
1443
1323
1520
1436
1349
 
TABLE T1a
VOLTAGE DROP (PER AMP PER METER)
Size of Conductor
2 Cables dc
2 Cables, 1-phase ac
3 or 4 Cables, 3-phase ac
Reference Methods
3 & 4
(enclosed in conduit etc,
in or on a wall)
Reference Methods
1 & 11
(clipped direct or
on trays touching)
Reference Methods
3 & 4
(enclosed in conduit etc,
in or on a wall)
Reference Methods
1,11 & 12
(in trefoil)
Reference Methods
1 & 11
(flat & touching)
1
2
3
4
5
6
7
mm²
mV/A/m
mV/A/m
mV/A/m
mV/A/m
mV/A/m
mV/A/m
1.5
31
31
31
27
27
27
2.5
19
19
19
16
16
16
4
12
12
12
10
10
10
6
7.9
7.9
7.9
6.8
6.8
6.8
10
4.7
4.7
4.7
4.0
4.0
4.0
16
2.9
2.9
2.9
2.5
2.5
2.5
 
 
r
x
z
r
x
z
r
x
z
r
x
z
r
x
z
25
1.85
1.85
0.31
1.90
1.85
0.19
1.85
1.60
0.27
1.65
1.60
0.165
1.60
1.60
0.19
1.60
35
1.35
1.35
0.29
1.35
1.35
0.18
1.35
1.15
0.25
1.15
1.15
0.155
1.15
1.15
0.18
1.15
50
0.99
1.00
0.29
1.05
0.99
0.18
1.00
0.87
0.25
0.90
0.86
0.155
0.87
0.86
0.18
0.87
70
0.68
0.70
0.28
0.75
0.68
0.175
0.71
0.60
0.24
0.65
0.59
0.150
0.61
0.59
0.175
0.62
95
0.49
0.51
0.27
0.58
0.49
0.170
0.52
0.44
0.23
0.50
0.43
0.145
0.45
0.43
0.170
0.46
120
0.39
0.41
0.26
0.48
0.39
0.165
0.43
0.35
0.23
0.42
0.34
0.140
0.37
0.34
0.165
0.38
150
0.32
0.33
0.26
0.43
0.32
0.165
0.36
0.29
0.23
0.37
0.28
0.140
0.31
0.28
0.165
0.32
185
0.25
0.27
0.26
0.37
0.26
0.165
0.30
0.23
0.23
0.32
0.22
0.140
0.26
0.22
0.165
0.28
240
0.19
0.21
0.26
0.33
0.20
0.160
0.25
0.185
0.22
0.29
0.17
0.140
0.22
0.17
0.165
0.24
300
0.155
0.175
0.25
0.31
0.16
0.160
0.22
0.15
0.22
0.27
0.14
0.140
0.195
0.135
0.160
0.21
400
0.12
0.14
0.25
0.29
0.13
0.155
0.20
0.125
0.22
0.25
0.11
0.135
0.175
0.110
0.160
0.195
500
0.093
0.12
0.25
0.28
0.105
0.155
0.185
0.100
0.22
0.24
0.09
0.135
0.160
0.088
0.160
0.180
630
0.072
0.10
0.25
0.27
0.086
0.155
0.175
0.088
0.21
0.23
0.074
0.135
0.150
0.071
0.160
0.170
800
0.056
 
 
 
0.072
0.150
0.170
 
 
 
0.062
0.130
0.145
0.059
0.155
0.165
1000
0.045
 
 
 
0.063
0.150
0.165
 
 
 
0.055
0.130
0.140
0.050
0.155
0.165
Note: r = conductor resistance at operating temperature,
z = impedance, x = reactance